Q & A of the Day – Lost earth in a bedroom – how to report it?

BookmarkThis 10.07.2008
SELECT
 

Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning lost earthing in a bedroom circuit and how to report it, is answered by SELECT:

How to report a bedroom circuit earth loss?
How to report a bedroom circuit earth loss?
pixel
Question: In carrying out an inspection and testing in a first floor flat, I found that a bedroom circuit has lost its earthing. The circuit hasn't been touched since the original installation approximately twenty years ago. In the periodic inspection report, under Observations & Recommendations, how should I report this? At present, what I may do is replace the light backbox from metal to plastic. To trace the problem would be a nightmare.

Answer: The Regulations are not retrospective, and under some previous installations it was not a requirement to provide an earthing terminal at connection of a lighting point.

However, it should be ensured that, under these circumstances, only Class 11 lighting accessories are installed - this would include the back box.

You should probably report this as a Deviation Code 4 - it does not comply with current regulations.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

http://www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Back

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: SELECT & James Hunt

Related information

Related contacts

More News...

Q & A of the Day – Can I run a separate supply to this machine socket-outlet?
Q & A of the Day – Must I buy new software for BS7671:2008 First Amendment?
Q & A of the Day – Should I use female bushes when mounting conduit box to metal trunking?
Q & A of the Day – Should I install an RCD to protect SWA cable at the house CU?
Q & A of the Day – What is the difference between City & Guilds 2391-10 and 2392 courses?
Q & A of the Day – Is there a problem with this client’s inspection report request?
Q & A of the Day – What is the right way to fit an SPD?
Q & A of the Day - Sockets by the seaside – what IP rating?
Q & A of the Day - What is required in terms of proximity of water/power supply cables?