Q & A of the Day – Lost earth in a bedroom – how to report it?

Select
 
Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This one, concerning lost earthing in a bedroom circuit and how to report it, is answered by SELECT:

How to report a bedroom circuit earth loss?
How to report a bedroom circuit earth loss?
pixel
Question: In carrying out an inspection and testing in a first floor flat, I found that a bedroom circuit has lost its earthing. The circuit hasn't been touched since the original installation approximately twenty years ago. In the periodic inspection report, under Observations & Recommendations, how should I report this? At present, what I may do is replace the light backbox from metal to plastic. To trace the problem would be a nightmare.

Answer: The Regulations are not retrospective, and under some previous installations it was not a requirement to provide an earthing terminal at connection of a lighting point.

However, it should be ensured that, under these circumstances, only Class 11 lighting accessories are installed - this would include the back box.

You should probably report this as a Deviation Code 4 - it does not comply with current regulations.

To see many more Q & A in Voltimum UK's Experts Area, please click on the link:

http://www.voltimum.co.uk/consult.php?universe=consult.index.questions

 Related contacts
SELECT
The Walled Garden, Bush Estate,
Midlothian, Scotland EH26 0SB
Tel: 0131 445 5577
Fax: 0131 445 5548
Email: admin@select.org.uk
Web: www.select.org.uk
blue arrow pointing right   SELECT

Source: SELECT & James Hunt
 Back

Related information

Related contacts

More News...

Q & A of the Day – Is a clean earth necessary for an IT server room?
Q & A of the Day – Can I supply the cooker hood from the main cooker supply?
Q & A of the Day – Calculating volt drop, which BS7671 table column should I use?
Q & A of the Day - Does a combi-boiler require supplementary bonding?
Q & A of the Day – Does agricultural machinery need isolation?
Q & A of the Day – Why is continuity of R1+R2 bigger than measured earth loop impedance?
Q & A of the Day – Why is this distribution board running at 40Hz?
Q & A of the Day – What testing on radial sockets from power busbars?
Q & A of the Day – What are protection requirements for socket in hazardous area?