Our Voltimum Experts answer your questions on a daily basis in our Technical Expertise area. This Question of the Day concerns a phase loop test and whether the measured value was correct. It is answered by SELECT:
|
| A Robin phase-tester - but what value? |
|
Question: I conducted a phase loop test on an existing installation and the value I got was 6.7ohms. Is this value low enough to allow a fault current to flow to operate the protective device? If not, what is the acceptable value?
Answer: Depending on the type of protective device, the maximum earth fault loop impedance values should comply with Table 41B2 or 41B1 from BS7671:2001.
To see many more Q & A in Voltimum UK's Experts Area, please click on the link: http://www.voltimum.co.uk/consult.php?universe=consult.index.questions
|