Requirements for cables concealed in a wall or partition – A brief overview

BookmarkThis
IEE
 

A new series of Regulations (522.6.6 - 522.6.8) have been introduced in the 17th Edition of the IEE Wiring Regulations concerning cables concealed in a wall or partition. These new Regulations introduce the concept of skilled person, instructed person and ordinary person.

Requirements for cables concealed in a wall or partition – A brief overview
pixel

RCD PROTECTION

It is now a requirement to protect cables concealed in a wall or partition (at a depth of less than 50 mm) by a 30 mA RCD where the installation is not intended to be under the supervision of a skilled or instructed person where other methods of protection, including the use of cables with an earthed metallic covering, earthed conduit/trunking or mechanical protection, can not be employed.

Irrespective of the depth, a cable in a partition where the construction includes metallic parts other than fixings shall be protected by a 30 mA RCD.

For example, this means that in a domestic installation, where insulated and sheathed cables are concealed in a wall at a depth of less than 50 mm and have no mechanical protection, they need to be installed within the safe zones and protected by a 30 mA RCD.

DEFINITIONS

Skilled person

A person with technical knowledge or sufficient experience to enable him/her to avoid dangers which electricity may create.

Instructed person

A person adequately advised or supervised by skilled persons to enable him/her to avoid dangers which electricity may create.

Ordinary person

A person who is neither a skilled person nor an instructed person.

WIRING SYSTEMS

To conform with the requirements of BS 7671, wiring systems must utilise cables complying with the relevant requirements of the applicable British Standard or Harmonised Standard.

Alternatively, if equipment complying with a foreign national standard, based on an IEC Standard is to be used, the designer or other person responsible for specifying the installation must verify that any differences between that standard and the corresponding British Standard or Harmonised Standard will not result in a lesser degree of safety than that afforded by compliance with the British Standard.

The effect of environmental conditions and general characteristics around various parts of the installation must be assessed to enable suitable electrical equipment, including the wiring system, to be specified.

For example, cables and equipment used in agricultural and horticultural premises should be installed away from areas or routes used by animals or be of a type to withstand such attack.

Any part of the fixed installation which may be exposed to a severe impact must be able to survive it. In workshops, for example, where heavy objects are moved, installation of wiring systems in traffic routes should be avoided or localised protection must be provided.

To read the full article, please see attachment below.

Originally published in Wiring Matters, Summer Edition 2008, written by Geoff Cronshaw.


 Back

 Downloadable attachment(s)
bluearrow  Requirements for cables concealed in a wall or partition - Wiring Matters article (388Kb PDF)

 Related links
blue arrow pointing right  IEE

 Related contacts
The Institution of Engineering and Technology
Savoy Place
London
WC2R 0BL
UK
Tel: +44 (0)20 7240 1871
Fax: +44 (0)20 7240 7735

 For latest electrical industry news, register for Voltimum's free newsletter.
Enter your email address here:
OK

Source: Wiring Matters Summer 2008 - Geoff Cronshaw

Related information

Downloadable attachment(s)
Related links
Related contacts

More News...

The Regulatory Reform (Fire Safety) Order 2005, BS 7671: 2008 and requirements for firefighters’ switches
In-Service Inspection and Testing of Electrical Equipment
Electrical Panels
Testing of Multipole RCDs
Protective Measures & Special Installations or Locations (Part 1)
Cables for temporary electrical installations
The use of "Arctic" cable
17th Edition launched - Special locations includes new requirements for bathrooms (IET Wiring Matters Spring 2008)
Energy efficiency of luminaires