CP-BBU 115-230VAC / 24VDC
|
|
 |
Product Ref.: 9916280024 EAN: 4032248217878
|
 |
UPS control unit, 24 V
 |
|
|
eClass 6.0
|
|
|
|
27-04-90-04
|
|
|
 |
|
|
Low Voltage Directive
|
|
|
|
73/ 23/ EWG
|
|
|
 |
|
|
Max. residual ripple
|
|
|
|
< 50 mVeff
|
|
|
 |
|
|
Surge protection [input]
|
|
|
|
Varistor
|
|
|
 |
|
|
Control at input voltage
|
|
|
|
0.2 %
|
|
|
 |
|
|
Ambient temperature (operational)
|
|
|
|
-20 °C...+50 °C
|
|
|
 |
|
|
ETIM30
|
|
|
|
EC001039
|
|
|
 |
|
|
ETIM20
|
|
|
|
EC001039
|
|
|
 |
|
|
Degree of efficiency at max. load
|
|
|
|
72 %
|
|
|
 |
|
|
eClass 5.0
|
|
|
|
27-24-22-13
|
|
|
 |
|
|
eClass 4.1
|
|
|
|
27-24-04-10
|
|
|
 |
|
|
Connection range
|
|
|
|
AWG26-12 (0.1-4.0 mm²)
|
|
|
 |
|
|
eClass 5.1
|
|
|
|
27-04-90-02
|
|
|
 |
|
|
Input fuse
|
|
|
|
2 A time-lag fuse (internal)
|
|
|
 |
|
|
Input frequency, max.
|
|
|
|
50/ 60 Hz
|
|
|
 |
|
|
Conductor connection system
|
|
|
|
Screw connection
|
|
|
 |
|
|
EMC standards
|
|
|
|
EN 61000-6-2, 3 EN 55011 EN 55022 EN 55024
|
|
|
 |
|
|
Protection class
|
|
|
|
IP 20
|
|
|
 |
|
|
Standards
|
|
|
|
EN 60950 IEC950 EN 50178
|
|
|
 |
|
|
Output voltage type
|
|
|
|
DC
|
|
|
 |
|
|
Input voltage (voltage mode input)
|
|
|
|
85...265 V AC; 120...300 V DC; typ.115...230 V AC ±10%
|
|
|
 |
|
|
DIN Rail compatibility
|
|
|
|
TS 35
|
|
|
 |
|
|
Status indication
|
|
|
|
Yellow LED (charging): BBU is loading battery Red LED (reversed battery): battery poles are reversed Red LED (error): no AC input voltage LED red (battery open): no battery is connected Yellow LED (low battery): battery voltage < 22 V DC
|
|
|
 |
|
|
making current limit
|
|
|
|
Thermistor
|
|
|
 |
|
|
Input current
|
|
|
|
1 A @ 115 V AC; 0.6 A @ 230 V AC
|
|
|
 |
|
|
Battery voltage
|
|
|
|
27,3 V
|
|
|
 |
|
|
Battery charging current
|
|
|
|
2 A
|
|
|
 |
|
|
Humidity at storage temperature
|
|
|
|
20 to 90%
|
|
|
 |
|
|
Humidity at operating temperature
|
|
|
|
20 - 85% RH without condensation
|
|
|
 |
|
|
Output current
|
|
|
|
max. 15 A / max. 9.0 A for power supply
|
|
|
 |
|
|
Mains failure bridge-over time for 230 V AC
|
|
|
|
190 ms
|
|
|
 |
|
|
Mains failure bridge-over time for 115 V AC
|
|
|
|
24 ms
|
|
|
 |
|
|
Version
|
|
|
|
UPS control unit, 24 V
|
|
|
 |
|
|
Output power, max.
|
|
|
|
360 W
|
|
|
 |
|
|
Approvals institutes
|
|
|
|
CSA; Cl. I Div .2; GOSTME25; CE
|
|
|
 |
|
|
Storage temperature
|
|
|
|
-20 °C...+85 °C
|
|
|
 |
|
|
Order No.
|
|
|
|
9916280024
|
|
|
 |
|
|
Part designation
|
|
|
|
CP-BBU 115-230VAC / 24VDC
|
|
|
 |
|
|
Ambient temperature (operational)
|
|
|
|
-20 °C...+50 °C
|
|
|
 |
|
|
EAN
|
|
|
|
4032248217878
|
|
|
 |
|
|
electrical isolation, output-earth
|
|
|
|
0.5 kV
|
|
|
 |
|
|
Qty.
|
|
|
|
1 ST
|
|
|
 |
|
|
electrical isolation, input-output
|
|
|
|
3 kV
|
|
|
 |
|
|
electrical isolation, I/O rail
|
|
|
|
3 kV
|
|
|
 |
|
|
Depth
|
|
|
|
127.5 mm
|
|
|
 |
|
|
electrical isolation, input-earth
|
|
|
|
1.5 kV
|
|
|
 |
|
|
Weight
|
|
|
|
950 g
|
|
|
 |
|
|
Switching frequency
|
|
|
|
100 kHz
|
|
|
 |
|
|
Clamping range, max.
|
|
|
|
4 mm²
|
|
|
 |
|
|
Height
|
|
|
|
127.5 mm
|
|
|
 |
|
|
Clamping range, nom.
|
|
|
|
4 mm²
|
|
|
 |
|
|
Clamping range, min.
|
|
|
|
0.1 mm²
|
|
|
 |
|
|
Width
|
|
|
|
72.5 mm
|
|
|
 |
|
|
Length
|
|
|
|
161 mm
|
|
|
 |
|
|
Output voltage
|
|
|
|
24 V
|
|
|
 |
|
 |
|
 |
|
|
|
 |
|
 |
|