eClass 6.0
|
|
|
|
27-04-90-04
|
|
|
 |
|
|
Max. residual ripple
|
|
|
|
120 mVPP
|
|
|
 |
|
|
Max. capacitance at output
|
|
|
|
8000 µF
|
|
|
 |
|
|
Rated control voltage
|
|
|
|
115 / 230 V AC (85...264 V AC, 110...370 V DC)
|
|
|
 |
|
|
rated output voltage
|
|
|
|
24 V DC ± 1 %
|
|
|
 |
|
|
Mains failure bridge-over time
|
|
|
|
11 ms @ 115 V AC / 50 ms @ 230 V AC
|
|
|
 |
|
|
Parallel connection option
|
|
|
|
Max. 3 devices (rated voltages are to be calibrated at ±20 mV)
|
|
|
 |
|
|
Overload protection
|
|
|
|
105 %...150 % Iconst of max. output load; automatic reset
|
|
|
 |
|
|
Control at 10...100% load
|
|
|
|
1 %
|
|
|
 |
|
|
Ambient temperature (operational)
|
|
|
|
-10 °C...+70 °C (derating from 55 °C)
|
|
|
 |
|
|
Surge protection [output]
|
|
|
|
Varistor
|
|
|
 |
|
|
ETIM20
|
|
|
|
EC001039
|
|
|
 |
|
|
Degree of efficiency at max. load
|
|
|
|
78 %
|
|
|
 |
|
|
eClass 4.1
|
|
|
|
27-24-04-10
|
|
|
 |
|
|
ETIM30
|
|
|
|
EC001039
|
|
|
 |
|
|
eClass 5.1
|
|
|
|
27-04-90-02
|
|
|
 |
|
|
eClass 5.0
|
|
|
|
27-24-22-13
|
|
|
 |
|
|
Installation advice
|
|
|
|
For side-by-side mounting, clearance: above/below > 8 mm
|
|
|
 |
|
|
EMC standards
|
|
|
|
EN 61000-6-2,-3,-4 EN 55011 EN 55022 EN 61000-3-2,-3
|
|
|
 |
|
|
Input frequency, max.
|
|
|
|
50/ 60 Hz
|
|
|
 |
|
|
Conductor connection system
|
|
|
|
Screw connection
|
|
|
 |
|
|
Input fuse
|
|
|
|
Fusible link 2.5 A (T) / 250 V
|
|
|
 |
|
|
Input voltage (voltage mode input)
|
|
|
|
85...264 V AC / 110...370 V DC
|
|
|
 |
|
|
Standards
|
|
|
|
EN 60950 (SELV) EN 50178 (PELV)
|
|
|
 |
|
|
Output voltage type
|
|
|
|
DC
|
|
|
 |
|
|
DIN Rail compatibility
|
|
|
|
TS 35
|
|
|
 |
|
|
Output voltage
|
|
|
|
(adjustable via poti)
|
|
|
 |
|
|
Status indication
|
|
|
|
Green LED
|
|
|
 |
|
|
Mounting position, installation notice
|
|
|
|
horizontally on terminal rail TS 35
|
|
|
 |
|
|
Input current at 230 Vac
|
|
|
|
500 mA
|
|
|
 |
|
|
Input current
|
|
|
|
500 mA at rated load @ 230 V AC
|
|
|
 |
|
|
Humidity at operating temperature
|
|
|
|
5...95 % (indoors), Tu = 40°C, no condensation
|
|
|
 |
|
|
making current limit
|
|
|
|
Yes
|
|
|
 |
|
|
Output current
|
|
|
|
2 A
|
|
|
 |
|
|
Input current at 115 Vac
|
|
|
|
500 mA
|
|
|
 |
|
|
Mains failure bridge-over time for 115 V AC
|
|
|
|
11 ms
|
|
|
 |
|
|
Output power, max.
|
|
|
|
48 W
|
|
|
 |
|
|
Mains failure bridge-over time for 230 V AC
|
|
|
|
50 ms
|
|
|
 |
|
|
Part designation
|
|
|
|
CP SNT 48W 24V 2A
|
|
|
 |
|
|
Approvals institutes
|
|
|
|
CE; CCSAUS; CULUS; CURUS; UL; CLASS2
|
|
|
 |
|
|
EAN
|
|
|
|
4032248411924
|
|
|
 |
|
|
Order No.
|
|
|
|
8739140000
|
|
|
 |
|
|
Version
|
|
|
|
Switched-mode power supplies
|
|
|
 |
|
|
Qty.
|
|
|
|
1 ST
|
|
|
 |
|
|
electrical isolation, output-earth
|
|
|
|
0.5 kV
|
|
|
 |
|
|
Storage temperature
|
|
|
|
-20 °C...+85 °C
|
|
|
 |
|
|
electrical isolation, I/O rail
|
|
|
|
4 kV
|
|
|
 |
|
|
electrical isolation, input-earth
|
|
|
|
1.5 kV
|
|
|
 |
|
|
electrical isolation, input-output
|
|
|
|
3 kV
|
|
|
 |
|
|
Weight
|
|
|
|
0.2 kg
|
|
|
 |
|
|
Depth
|
|
|
|
80 mm
|
|
|
 |
|
|
Height
|
|
|
|
90.5 mm
|
|
|
 |
|
|
Clamping range, min.
|
|
|
|
0.5 mm²
|
|
|
 |
|
|
Clamping range, max.
|
|
|
|
4 mm²
|
|
|
 |
|
|
Length
|
|
|
|
62.5 mm
|
|
|
 |
|
|
Clamping range, nom.
|
|
|
|
2.5 mm²
|
|
|
 |
|
|
Output voltage, max.
|
|
|
|
28 V
|
|
|
 |
|
|
Width
|
|
|
|
70 mm
|
|
|
 |
|
|
Output voltage, min.
|
|
|
|
15 V
|
|
|
 |