eClass 6.0
|
|
|
|
27-04-90-04
|
|
|
 |
|
|
Max. capacitance at output
|
|
|
|
40000 µF
|
|
|
 |
|
|
Power factor correction
|
|
|
|
No
|
|
|
 |
|
|
Max. residual ripple
|
|
|
|
< 100 mVPP / bandwidth 20 MHz
|
|
|
 |
|
|
Low Voltage Directive
|
|
|
|
73/ 23/ EWG
|
|
|
 |
|
|
Mains failure bridge-over time
|
|
|
|
20 ms @ 115 V AC / 20 ms @ 230 V AC
|
|
|
 |
|
|
Control at 10...100% load
|
|
|
|
< 2 %
|
|
|
 |
|
|
Parallel connection option
|
|
|
|
Recommended with diode module
|
|
|
 |
|
|
Overload protection
|
|
|
|
105 %..130 % Iconst of max. output load; automatic reset
|
|
|
 |
|
|
Control at input voltage
|
|
|
|
0.5 %
|
|
|
 |
|
|
Surge protection [output]
|
|
|
|
29...34 V
|
|
|
 |
|
|
Ambient temperature (operational)
|
|
|
|
-10 °C...+70 °C (derating from 55 °C)
|
|
|
 |
|
|
Surge protection [input]
|
|
|
|
Varistor
|
|
|
 |
|
|
Degree of efficiency at max. load
|
|
|
|
84 %
|
|
|
 |
|
|
ETIM30
|
|
|
|
EC001039
|
|
|
 |
|
|
ETIM20
|
|
|
|
EC001039
|
|
|
 |
|
|
eClass 5.0
|
|
|
|
27-24-22-13
|
|
|
 |
|
|
eClass 4.1
|
|
|
|
27-24-04-10
|
|
|
 |
|
|
eClass 5.1
|
|
|
|
27-04-90-02
|
|
|
 |
|
|
Installation advice
|
|
|
|
Clearance: above/below ≥ 3 cm
|
|
|
 |
|
|
Connection range
|
|
|
|
AWG26-12 (0.1-4.0 mm²)
|
|
|
 |
|
|
Input frequency, max.
|
|
|
|
50/ 60 Hz
|
|
|
 |
|
|
Input fuse
|
|
|
|
Fusible link 4 A (T) / 250 V
|
|
|
 |
|
|
EMC standards
|
|
|
|
EN 61000-6-2, 3 EN 55011 EN 55022 EN 55024
|
|
|
 |
|
|
Standards
|
|
|
|
EN 60950 (SELV)
|
|
|
 |
|
|
Conductor connection system
|
|
|
|
Screw connection
|
|
|
 |
|
|
Protection class
|
|
|
|
IP 20
|
|
|
 |
|
|
Output voltage type
|
|
|
|
DC
|
|
|
 |
|
|
Input voltage (voltage mode input)
|
|
|
|
88...132 V AC/176...264 V AC selectable; 250...370 V DC
|
|
|
 |
|
|
Status indication
|
|
|
|
Green LED
|
|
|
 |
|
|
DIN Rail compatibility
|
|
|
|
TS 35
|
|
|
 |
|
|
Mounting position, installation notice
|
|
|
|
horizontally on terminal rail TS 35
|
|
|
 |
|
|
Output voltage
|
|
|
|
(adjustable via poti)
|
|
|
 |
|
|
Output current
|
|
|
|
5 A
|
|
|
 |
|
|
Input current
|
|
|
|
3 A @ 115 V AC / 2 A @ 230 V AC
|
|
|
 |
|
|
Mains failure bridge-over time for 115 V AC
|
|
|
|
20 ms
|
|
|
 |
|
|
Status relay / CO contact
|
|
|
|
250 V AC (max. 30 V DC) / 1 A
|
|
|
 |
|
|
Mains failure bridge-over time for 230 V AC
|
|
|
|
20 ms
|
|
|
 |
|
|
Storage temperature
|
|
|
|
-20 °C...+85 °C
|
|
|
 |
|
|
Version
|
|
|
|
Switched-mode power supplies
|
|
|
 |
|
|
electrical isolation, output-earth
|
|
|
|
0.5 kV
|
|
|
 |
|
|
electrical isolation, input-earth
|
|
|
|
1.5 kV
|
|
|
 |
|
|
electrical isolation, input-output
|
|
|
|
3 kV
|
|
|
 |
|
|
Part designation
|
|
|
|
CP SNT 120W 24V 5A
|
|
|
 |
|
|
Approvals institutes
|
|
|
|
CULUS; CURUS; GERMLLOYD; GOSTME25; CE
|
|
|
 |
|
|
EAN
|
|
|
|
4032248380831
|
|
|
 |
|
|
Order No.
|
|
|
|
8708670000
|
|
|
 |
|
|
Depth
|
|
|
|
100 mm
|
|
|
 |
|
|
Qty.
|
|
|
|
1 ST
|
|
|
 |
|
|
Height
|
|
|
|
125 mm
|
|
|
 |
|
|
Weight
|
|
|
|
0.65 kg
|
|
|
 |
|
|
Clamping range, min.
|
|
|
|
0.13 mm²
|
|
|
 |
|
|
Clamping range, max.
|
|
|
|
4 mm²
|
|
|
 |
|
|
Length
|
|
|
|
110 mm
|
|
|
 |
|
|
Clamping range, nom.
|
|
|
|
2.5 mm²
|
|
|
 |
|
|
Width
|
|
|
|
65.5 mm
|
|
|
 |
|
|
Output voltage, min.
|
|
|
|
24 V
|
|
|
 |
|
|
Output voltage, max.
|
|
|
|
28 V
|
|
|
 |
|
|
Output power, max.
|
|
|
|
120 W
|
|
|
 |