Laminated aluminium tape screen bonded to sheath and in contact with full size tinned annealed copper circuit protective conductor which provides automatic screen earthing.
Sheath
Robust thermoplastic LSOH sheath
Colour - red or white. Other colours to special order.
For external exposure the use of a white sheath is recommended.
Approvals
In addition to approvals to BS 7629-1 and BS6387 Category CWZ, FP200 Gold® has received BASEC and LPCB approval to BS5839-1:2002 for 'standard' applications. This includes approval to BS EN 50200 Classification PH30 and the new integrated fire, schock and water test BS8434-1 for 30 minutes FP200 Gold® is also approved to BS EN 50200 Classification PH60 as required by BS5266-1:2005.
Data Capability
FP200 Gold® has excellent data/signal transmission characteristics making it ideal for voice alarms, addressable and networked systems.
Installation
In accordance with the new BS5839-1 and BS5266-1 requirements, cables must be supported by a fixing that can withstand the same fire conditions as the cable. To meet this requirement the use of Prymian AP LSOH® coated metal P - clips or the new FP Firefix ™ rapid fixing system is recommended.