H07RN-F LINEAX 3x16 cut to length

 
Product Ref.: 10082210
EAN: 3427680031853

Application

LINEAX flexible cable is intended for installations withmoving equipment, electric appliances and for building sites. Thecable may be rated 0,6/1 kV where the installation has built-inprotection and for motors in lifting appliances - machine tools -etc.

This cable can be used in refrigerating installations.

 

Installation

This cable can be installed in open air or be buried but withextra mechanical protection.

Conductors laid up 

Assembled conductors.

Marking

USE <'har>N (x ou G) S LINEAX

  • N = number of cores
  • G = with Green-Yellow
  • x = without Green-Yellow
  • S = section in mm²

Nota

Max continuous operating conductor temperature in normal use:

+60°C   ( in every case of mobile installation)

+85°C   ( fixed protected installation )

+200°C ( in short circuit )

 

Permissible current rating is measured for an ambienttemperature of 30°C and a maximum operating and conductortemperature of 85°C . For other temperature please refer tocorrection factors .


 
Main characteristics
Standards HD 22.4, HD 516, IEC 60245-4 type 66
Conductor cross-section 16 mm²
Number of cores 3
Permissible current rating in open air 102 A
Maximum outer diameter 27.6 mm
Minimum outer diameter 21.8 mm
Minimum dynamic operating bending radius 165.6 mm
Minimum static operating bending radius 82.8 mm
Max. conductor temperature in service 60 °C
Operating temperature, range -25 °C - 55 °C
Short-circuit max. conductor temperature 200 °C
Approximate weight 910 kg/km